Moulded case current transformers for the measurement of AC currents from 50A to 4800A.
They are made of a non-flammable plastic material. This new range of current transformers has been designed for an easy installation: all transformers can be delivered with DIN rail clips. They are equipped as standard with a sealable terminal cover to comply with the most demanding safety requirements. This range include current transformers for measuring duties and is suitable for every simple application.
Technical data
Highest voltage for equipment
750 V
power-frequency withstand voltage
3000 V
primary current Ipn
50 to 4800A
secondary current Isn
5 or 1A
Frequency
50 or 60 Hz
Rated output
1 to 15 VA
Accuracy class
0.5 - 1 - 3
Security factor
5 to 30
Continuous thermal current
1.2 Ipn
short-time thermal current Ith
80 Ipn . 1s or 80 Ipn.1s
Dynamic current Idyn
2.5Ith
Insulation class
A
Altitude
1000 m
Ambient temperature
-5C° to + 40 C°
-25C° to + 40 C°
-40C° to + 40 C°
Standards
IEC60044-1, IEC61869-2,ANSI C57.13
Other characteristics on request
Highest voltage for equipment
Up to 1200 V
power-frequency withstand voltage
Up to 6 KV
secondary current Isn
0.01 to 0.5 A
Frequency
1 to 10000 Hz
Continues thermal current
1.2 to 1.5Ipn and 2Ipn
Ambient temperature
-40C° to + 70 C°
Standard
ANSI C57.13 – CAN3 C13 – AS 1675
Selection table:
selection table
Ip
Type
Output
A
Maximum VA
cl3
cl1
Cl0.5
50
L3A
1
L4A
1.25
60
L3A
1.25
L4A
2.5
75
L3A
2.5
L4A
2.5
100
L3A
3.75
2.5
L4A
3.75
2.5
125
L3A
3.75
2.5
L4A
3.75
2.5
150
L3A
5
3.75
2.5
L4A
5
3.75
2.5
200
L3A
5
3.75
2.5
L4A
7.5
5
2.5
250
L3A
10
7.5
5
L4A
10
7.5
5
300
L3A
10
7.5
7.5
L4A
15
7.5
5
400
L3A
15
10
10
L4A
15
15
10
500
L3A
15
15
15
L4A
15
15
10
600
L3A
15
15
15
L4A
15
15
10
750
L4A
15
15
15
1000
L4A
15
15
15
*This document is the property of Pars Shar and maybe changed without prior notice*