Double pole voltage transformer vacuum moulded in self-extinguishing epoxy resin for measurement of AC voltages between phases up to 36KV with rated outputs up to 100 VA cl0.2 or 150 VA cl0.5.
This range is also suitable for the power supply of auxiliaries up to 2500 VA CLA.
Technical data
Rated insulation level
3.6/16/45 Kv to 36/70/170 Kv
primary voltage Upn
Up to 36000V
secondary voltage Usn
100 - 110 V
Frequency
50 or 60 Hz
Rated output
Up to 100VA cl0.2 -150VA cl0.5 -200VA cl1
Accuracy class
0.2 - 0.5 - 1 - 3 - 3P - 6P
Voltage factor
1.2 Upn continuously
Thermal limiting output
Up to 5000 VA
Insulation class
A
Altitude
1000 m
Ambient temperature
-5C° to + 40 C°
-25C° to + 40 C°
-40C° to + 40 C°
Standards
IEC60044-2, IEC61869-3
Other characteristics on request
Secondary Voltage Usn
10 to 600 V
Ambient temperature
Up to + 110 °C
Scondary windings
Up to 3 secondary windings
Selection table:
Type
Un
Up
Rated output
Thermal output
kv
kv
maximum VA
VA
Cl0.5
Cl1
Cl3
RM5
7.2/20/60
up to 6.6
50
50
100
up to 300
RM7
7.2/20/60
up to 6.6
50
100
150
up to 300
RM10
12/28/75
up to 11
50
75
150
up to 400
RM15
17.5/38/95
up to 15
50
150
300
up to 750
RM30
36/70/170
up to 35
150
200
500
up to 2500
Dimensions:
Type
weight
k
B
C
D
E
F
kg
mm
mm
mm
mm
mm
mm
RM5
11
49
181
135
251
190
160
RM7
16
54.5
184
120
270
-
180
RM10
16
63
210
163
277
240
185
RM15
21
-
250
168
300
-
-
RM30
52
67
340
248
380
-
313