Medium voltage, voltage transformers , RU series

Download catalog

Download Type Test

Indoor

3.6 – 7.2 – 12 – 17.5 – 24 – 36 KV

Primary voltage up to 33000: √3

More details

Technical data

MV VT's type:1-pole
Rated insulation level:3.6/16/45to36/70/250
Primary voltage Upn:Up to 33000:√3
Secondary voltage Usn:3√110 - 3√100
Frequency:50or60
Rated output:Up to 200 VA cl 0.2-500 VA cl 0.5 -1000 VA cl 1
Accuracy class:0.2-0.5-1-3-3P-6P
Voltage factor:1.2Upn continuously
Thermal limiting output:Up to 500
Insulation class:A
Altitude:1000
Ambient temperature:-5C° to + 40 C° -25C° to + 40 C° -40C° to + 40 C°
Standards:IEC60044-2, IEC61869-3

Other characteristics on request

Secondary voltage Usn*:3√:380 - 3√:24
Voltage factor*:1.9Upn 8h
Ambient temperature*:Up to 110 C
secondary winding:Up to 3 secondary windings
Residual voltage winding:Delta convection - 100:3 V 50 VA Cl3

Other

Indoor or outdoor:Indoor